Under FSD Circular Letter No. 3/2026, composite and domestic buildings of six storeys or below that were built on or before March 1987 and are regulated by the Fire Safety (Buildings) Ordinance (Cap. 572) can use an IoT fire detection system plus portable fire extinguishers instead of hose reel and manual fire alarm systems. All other requirements under the Ordinance stay the same.
Which buildings qualify?
- Composite or domestic buildings regulated by the Fire Safety (Buildings) Ordinance (Cap. 572).
- Built on or before March 1987 (the Ordinance's "target buildings").
- Six storeys or below.
- Only the hose reel and manual fire alarm requirements are replaced; other applicable requirements, such as sprinklers, emergency lighting and automatic cut-off for mechanical ventilation, are unchanged.
What the system includes
Wireless multi-sensor detectors
Installed at the entrance of each unit and in the common areas of every floor; they detect smoke and carbon monoxide.
Gateways
Placed in common areas, combining manual call points, alarm sounders and signal transmission, with two SIM cards on different networks.
Monitoring platform
Receives gateway signals, monitors system status and passes fire alarm signals to the Fire Services Communications Centre through CFATS, with all signals also sent to the FSD's server by API.
Mobile app and extinguishers
Lets firefighters view and control the system on site; each floor also needs at least two 5 kg dry-powder portable extinguishers.
What happens when there is a fire
- 01
Detection or call point
A detector senses fire, or someone presses a manual call point.
- 02
Whole-building alarm
Sounders go off to tell occupants to evacuate, and the signal goes to a gateway by local wireless link.
- 03
Monitoring platform
The gateway sends the location and device status to the monitoring platform over an external network.
- 04
FSD alerted automatically
The platform passes the fire alarm signal to the Fire Services Communications Centre through CFATS for prompt dispatch.
- 05
Firefighters on site
Firefighters use the mobile app to view and control the system.
Who is responsible for what
- The IoT FDS service provider coordinates the system and provides and operates the monitoring platform.
- A registered fire service installation contractor installs, maintains, inspects and repairs the fire service installation components on the premises.
- The CFATS service provider supplies the communication service that passes fire alarm signals to the FSD quickly and reliably.
Is there a subsidy?
Yes. The FSD's alternative solution falls within the Fire Safety Improvement Works Subsidy Scheme. Eligible applicants can receive up to 60% of the cost of eligible works and consultancy fees, or the subsidy cap for that category of building, whichever is lower (Building Rehab Platform, 10 September 2026).
How to apply
- 01
Submit an expression of interest
Download the FSD's "Expression of Interest for IoT Fire Detection System" form and submit it to the FSD Building Improvement Support Centre.
- 02
Choose a service provider
Refer to the FSD's list of service providers interested in providing IoT FDS and compare their proposals.
- 03
Survey and design
Arrange a site survey to decide detector and gateway numbers, positions and wireless coverage.
- 04
Apply for the subsidy
If eligible, apply under the Fire Safety Improvement Works Subsidy Scheme.
- 05
Install, test and go live
After installation and acceptance testing, the system starts 24-hour monitoring.
Official sources