BLUTA步泰科技

FOR BUILDING OWNERS · UPDATED OCT 2026

A guide for owners of older buildings: meeting fire safety requirements with an IoT fire detection system

If your building has received Fire Safety Directions requiring hose reels and a manual fire alarm system, an IoT fire detection system (IoT FDS) may be a simpler alternative.

SHORT ANSWER

Under FSD Circular Letter No. 3/2026, composite and domestic buildings of six storeys or below that were built on or before March 1987 and are regulated by the Fire Safety (Buildings) Ordinance (Cap. 572) can use an IoT fire detection system plus portable fire extinguishers instead of hose reel and manual fire alarm systems. All other requirements under the Ordinance stay the same.

Which buildings qualify?

  • Composite or domestic buildings regulated by the Fire Safety (Buildings) Ordinance (Cap. 572).
  • Built on or before March 1987 (the Ordinance's "target buildings").
  • Six storeys or below.
  • Only the hose reel and manual fire alarm requirements are replaced; other applicable requirements, such as sprinklers, emergency lighting and automatic cut-off for mechanical ventilation, are unchanged.

What the system includes

01

Wireless multi-sensor detectors

Installed at the entrance of each unit and in the common areas of every floor; they detect smoke and carbon monoxide.

02

Gateways

Placed in common areas, combining manual call points, alarm sounders and signal transmission, with two SIM cards on different networks.

03

Monitoring platform

Receives gateway signals, monitors system status and passes fire alarm signals to the Fire Services Communications Centre through CFATS, with all signals also sent to the FSD's server by API.

04

Mobile app and extinguishers

Lets firefighters view and control the system on site; each floor also needs at least two 5 kg dry-powder portable extinguishers.

What happens when there is a fire

  1. 01

    Detection or call point

    A detector senses fire, or someone presses a manual call point.

  2. 02

    Whole-building alarm

    Sounders go off to tell occupants to evacuate, and the signal goes to a gateway by local wireless link.

  3. 03

    Monitoring platform

    The gateway sends the location and device status to the monitoring platform over an external network.

  4. 04

    FSD alerted automatically

    The platform passes the fire alarm signal to the Fire Services Communications Centre through CFATS for prompt dispatch.

  5. 05

    Firefighters on site

    Firefighters use the mobile app to view and control the system.

Who is responsible for what

  • The IoT FDS service provider coordinates the system and provides and operates the monitoring platform.
  • A registered fire service installation contractor installs, maintains, inspects and repairs the fire service installation components on the premises.
  • The CFATS service provider supplies the communication service that passes fire alarm signals to the FSD quickly and reliably.

Is there a subsidy?

Yes. The FSD's alternative solution falls within the Fire Safety Improvement Works Subsidy Scheme. Eligible applicants can receive up to 60% of the cost of eligible works and consultancy fees, or the subsidy cap for that category of building, whichever is lower (Building Rehab Platform, 10 September 2026).

Building Rehab Platform: subsidy arrangement for IoT FDS ↗

How to apply

  1. 01

    Submit an expression of interest

    Download the FSD's "Expression of Interest for IoT Fire Detection System" form and submit it to the FSD Building Improvement Support Centre.

  2. 02

    Choose a service provider

    Refer to the FSD's list of service providers interested in providing IoT FDS and compare their proposals.

  3. 03

    Survey and design

    Arrange a site survey to decide detector and gateway numbers, positions and wireless coverage.

  4. 04

    Apply for the subsidy

    If eligible, apply under the Fire Safety Improvement Works Subsidy Scheme.

  5. 05

    Install, test and go live

    After installation and acceptance testing, the system starts 24-hour monitoring.

Official sources

  • FSD Building Improvement Support Centre hotline: 2272 9112 (Monday to Saturday, 9 am to 8 pm, except public holidays).

Is your building suitable?

Tell us the building address, number of floors and units, and whether you have received Fire Safety Directions. We will give you an initial assessment.

Contact BLUTA